Radiant Tube Pressure Drop Calculator

Estimate single-phase tube pressure loss using Darcy–Weisbach, laminar or Colebrook friction, and supplied fitting loss coefficients.

Preliminary engineering estimate. Review the model assumptions and applicability limits below before using results.

1. Fluid state and flow
2. Tube path and fitting assumptions

Not calculated. Press Calculate; editing any input clears previous results.

Calculation Results

ParameterCalculated ValueUnit
Mass flow per path—kg/s
Mean flow velocity—m/s
Reynolds number——
Flow regime——
Darcy friction factor——
Relative roughness——
Straight tube pressure loss—Pa
Return bend pressure loss—Pa
Other fitting pressure loss—Pa
Total irreversible pressure loss—Pa
Signed elevation pressure change—Pa
Total inlet-to-outlet static pressure decrease—Pa
Total static pressure decrease—bar
Estimated outlet absolute pressure—Pa
Inlet Mach number (gas mode only)——

Input Summary

ParameterInput Value
Fluid phaseSingle-phase liquid
Total mass flow (kg/s)0.007853982
Equal parallel flow paths1
Assumed constant density (kg/m³)1,000
Dynamic viscosity (Pa·s)0.001
Inlet absolute pressure (bar absolute)1
Gas heat capacity ratio (gas mode)1.4
Tube inside diameter (m)0.01
Straight length per flow path (m)1
Absolute internal roughness (m)0
Return bends per path1
Assumed loss coefficient per return bend2
Other fitting loss coefficients (sum)0
Outlet elevation above inlet (signed) (m)0

Method and formulas

v = ṁ/(npaths ρ πDi²/4); Re = ρvDi/μ. Darcy f = 64/Re for Re < 2300.

For 4000 ≤ Re ≤ 10⁸: 1/√f = −2log₁₀[ε/(3.7Di) + 2.51/(Re√f)] (Colebrook, solved iteratively).

ΔPstraight = f(L/Di)ρv²/2; ΔPfittings = ΣKρv²/2; ΔPstatic = ΔPloss + ρgΔz; Pout = Pin − ΔPstatic.

Assumptions and applicability

Single-phase, fully developed flow with constant user-supplied density and viscosity; equal flow division. Transitional Re 2300–4000 is unsupported; turbulent range capped at 10⁸ and relative roughness at 0.05 as implementation limits. Gas use additionally requires γ > 1, inlet Mach < 0.3 and pressure change ≤10% of inlet pressure. No two-phase, flashing, cavitation, heated-gas acceleration or compressible solver. Fitting K values are supplied assumptions. Preliminary calculation only. API 560 and API 530 public scope previews provide context; this tool does not establish API compliance or replace detailed heater, mechanical or materials design.

Frequently asked questions

Which friction factor is reported?

The Darcy factor, four times the Fanning factor. Transitional flow is rejected instead of interpolating an unverified correlation.

Can this evaluate two-phase heater coils?

No. Two-phase flow is explicitly rejected; heated compressible or flashing streams require a suitable coupled flow model.

Engineering references

  1. DOE Fundamentals Handbook, Volume 3 — Fluid Flow (1992)
  2. COMSOL Pipe Flow theory — Darcy–Weisbach and Colebrook equations
  3. API 560 public scope preview — fifth edition (2016); historical scope context
  4. API 530 public scope preview — seventh edition (2015); historical scope context