Burner Pressure Drop Calculator
Separate external fuel/air line friction losses from internal burner pressure requirements supported by qualified vendor coefficients.
Preliminary engineering estimate. Review the model assumptions and applicability limits below before using results.
Not calculated. Press Calculate; editing any input clears previous results.
Calculation Results
| Parameter | Calculated Value | Unit |
|---|---|---|
| Fuel line — Hydraulic / inside diameter | — | m |
| Fuel line — Flow area | — | m² |
| Fuel line — Velocity | — | m/s |
| Fuel line — Reynolds number | — | — |
| Fuel line — Darcy friction factor | — | — |
| Fuel line — Straight line friction loss | — | Pa |
| Fuel line — Fitting pressure loss | — | Pa |
| Fuel line — Total external line pressure loss | — | Pa |
| Fuel line — Burner connection absolute pressure | — | Pa |
| Fuel line — Inlet Mach number (gas only) | — | — |
| Air line — Hydraulic / inside diameter | — | m |
| Air line — Flow area | — | m² |
| Air line — Velocity | — | m/s |
| Air line — Reynolds number | — | — |
| Air line — Darcy friction factor | — | — |
| Air line — Straight line friction loss | — | Pa |
| Air line — Fitting pressure loss | — | Pa |
| Air line — Total external line pressure loss | — | Pa |
| Air line — Burner connection absolute pressure | — | Pa |
| Air line — Inlet Mach number (gas only) | — | — |
| Fuel connection pressure above chamber | — | Pa |
| Air connection pressure above chamber | — | Pa |
| Vendor-qualified internal fuel pressure loss | — | Pa |
| Vendor-qualified internal air pressure loss | — | Pa |
| Fuel pressure margin after vendor loss | — | Pa |
| Air pressure margin after vendor loss | — | Pa |
| Line / vendor performance scope | — | — |
Input Summary
| Parameter | Input Value |
|---|---|
| Fuel line phase | Single-phase gas |
| Fuel mass flow rate (kg/s) | 0.05 |
| Fuel representative density (kg/m³) | 0.8 |
| Fuel dynamic viscosity (Pa·s) | 0.000011 |
| Fuel inside diameter (round line) (m) | 0.05 |
| Fuel straight line length (m) | 10 |
| Fuel absolute roughness (m) | 0.000045 |
| Fuel fitting loss coefficient sum | 2 |
| Fuel inlet absolute pressure (bar absolute) | 3 |
| Fuel heat capacity ratio (gas) | 1.3 |
| Air duct cross-section | Round pipe / duct |
| Combustion air mass flow rate (kg/s) | 0.8 |
| Combustion air representative density (kg/m³) | 1.2 |
| Combustion air dynamic viscosity (Pa·s) | 0.000018 |
| Combustion air inside diameter (round line) (m) | 0.3 |
| Combustion air straight line length (m) | 10 |
| Combustion air absolute roughness (m) | 0.000045 |
| Combustion air fitting loss coefficient sum | 2 |
| Combustion air inlet absolute pressure (bar absolute) | 1.05 |
| Combustion air heat capacity ratio (gas) | 1.4 |
| Air rectangular duct clear width (m) | 0.3 |
| Air rectangular duct clear height (m) | 0.3 |
| Combustion chamber absolute pressure (bar absolute) | 1.01325 |
| Internal burner pressure model | Vendor data unavailable |
| Vendor internal fuel coefficient (connection velocity basis) | 1 |
| Vendor internal air coefficient (connection velocity basis) | 5 |
Method and formulas
Round line: A = πD²/4. Rectangular air duct: A = WH; Dh =2WH/(W+H). v = ṁ/(ρA); Re = ρvDh/μ.
External line: ΔP = [fD L/Dh +ΣK]ρv²/2. Darcy fD =64/Re below Re2300; Colebrook at Re4000–10⁸. Connection pressure = inlet absolute pressure −external losses.
Internal burner loss is Unavailable unless qualified vendor K values are supplied on the corresponding connection velocity basis: ΔPvendor = Kvendorρv²/2. Margin = Pconnection −Pchamber −ΔPvendor. These coefficients are not universal burner correlations.
Assumptions and applicability
Constant representative properties, steady fully developed flow, no elevation change. Fuel round pipe supports single-phase gas/liquid; air supports round/rectangular ducts. Rectangular hydraulic-diameter treatment is restricted to turbulent flow; laminar noncircular flow is not approximated by 64/Re. Transitional Re2300–4000 and relative roughness >0.05 are rejected. Gas Mach <0.3 and external loss ≤10% inlet pressure. No heated/compressible integration, choking, valve capacity or two-phase model. Internal coefficients must be qualified for the exact burner, state, flow and pressure reference; illustrative examples are not design data. Curves require separate vendor interpretation and are not interpolated here. Preliminary selection only; no API 560 compliance or vendor burner performance certification. Flame geometry, emissions, stability, controls, materials and installation design require separate assessment.
Frequently asked questions
Is this a complete or certified burner design?
No. This tool performs the stated preliminary calculation. Final selection requires qualified vendor performance, combustion controls and the applicable design review.
What happens when I change an input?
Results clear immediately. Press Calculate to evaluate current inputs. Reset and Load Example restore the illustrated input set.