Fuel Consumption Calculator

Calculate fuel mass flow and qualified-state volumetric flow from fired heat input and a consistently selected LHV or HHV.

Preliminary engineering estimate. Review the model assumptions and applicability limits below before using results.

1. Fired input and heating value
2. Qualified fuel volume properties

Not calculated. Press Calculate; editing any input clears previous results.

Calculation Results

ParameterCalculated ValueUnit
Fuel mass flow—kg/s
Fuel mass flow—kg/h
Fuel mass flow—lb/h
Fuel density at specified state—kg/m³
Fuel volumetric flow at specified state—m³/s
Fuel volumetric flow at specified state—m³/h
Fuel energy input on selected basis—W
Fuel energy balance residual—W
Heating value and volume basis——

Input Summary

ParameterInput Value
Required fired input (already includes any design margin) (kW)1,000
Fired input and heating-value basisLower heating value
Heating value on selected basis (kJ/kg)50,000
Volumetric property modelSingle-phase gas
Gas volume reference temperature (K)288.15
Gas volume reference absolute pressure (bar absolute)1.01325
Gas molecular weight (kg/kmol)16.043
Qualified gas compressibility factor1
Supplied fuel density (density mode) (kg/m³)800

Method and formulas

ṁfuel = Qfired/HV; energy input = ṁfuel HV. No additional efficiency or design margin is applied here.

Gas: ρ = PM/(Z×8314.46261815324×T), M in kg/kmol. Qualified-density mode uses the supplied density. V̇ = ṁ/ρ.

Assumptions and applicability

HV must match the stated LHV/HHV fired-input basis. There is no automatic LHV-to-HHV conversion. Gas volume is at the explicitly entered temperature, absolute pressure and Z, not an unspecified normal/standard condition. Density mode supports a qualified liquid or gas density. Gas Z 0.2–2 is an implementation guard; phase equilibrium, flash, gas properties and heating value are not predicted. Preliminary selection only; no API 560 compliance or vendor burner performance certification. Flame geometry, emissions, stability, controls, materials and installation design require separate assessment.

Frequently asked questions

Is this a complete or certified burner design?

No. This tool performs the stated preliminary calculation. Final selection requires qualified vendor performance, combustion controls and the applicable design review.

What happens when I change an input?

Results clear immediately. Press Calculate to evaluate current inputs. Reset and Load Example restore the illustrated input set.

Engineering references

  1. Cantera — LHV and HHV definitions
  2. DOE / IHEA — Process Heating Sourcebook (2007)
  3. API 560 — public scope, sixth edition (2026)