Plate Type Air Preheater Design Calculator

Estimate fired-heater air preheat, plate count, and core and system pressure loss. Compare longitudinal, serial-module, and orthogonal crossflow arrangements.

Leave both outlet targets blank to predict performance. Enter an outlet target to check thermal sizing. The starting values illustrate a single-pass smooth-plate core.

Single-pass counterflow through alternating channels. Outer plates close the stack.
Hot Flue Gas
Combustion Air
Plate Geometry
Design Criteria

Pressure-drop checks cover the core only. Leave the verification boxes clear when using illustrative coefficients.

Plate surface
Flow configuration
Explicit serial and parallel pass paths

{"modules":[{"plates":3,"flow":"counterflow"},{"plates":3,"flow":"counterflow"}],"gas":[{"fraction":1,"modules":[1,2]}],"air":[{"fraction":0.5,"modules":[1]},{"fraction":0.5,"modules":[2]}]}

Custom paths use prescribed flows. Branch balancing, connection losses, and plate-count sizing require a separate design check.

System components

Add external ducts and documented fittings separately from the core. Assign the total-loss coefficient to its reference section. Parallel groups require documented path losses between shared total-pressure nodes.

Equations and assumptions

Energy balance. Convert mass flow to kg/s and specific heat to J/(kg·K). C = ṁcₚ, Qmax = Cmin(Tg,in − Ta,in), NTU = UA/Cmin and Cᵣ = Cmin/Cmax. Core duty = εQmax. The gas cools by Q/Cg and air warms by Q/Ca in the core. The loss percentage derates delivered air duty downstream of the core. Use properties at representative bulk conditions. The model holds them constant.

Channel balances and sizing. Each plate transfers U·width·Δx times the adjacent cell-midpoint temperature difference. The solver sweeps each channel from its prescribed inlet, with opposite inlet ends in counterflow, and mixes the channel outlets by heat capacity rate. Successive meshes must agree in outlet temperatures within 0.01 K and in both duties within 0.001% of theoretical maximum duty. The gas and core air duties are computed independently. Effectiveness is gas duty divided by maximum duty. A gas target is a maximum and a delivered-air target is a minimum. If both are entered, their implied duties must agree within 1%. The search re-rates odd and even stacks up to 256 plates, subject to a numerical work limit. Ideal target UA and area are diagnostics.

Temperature differences. Counterflow pairs hot inlet with core air outlet and hot outlet with air inlet. Parallel flow pairs the two inlets and the two core outlets. LMTD = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), with the common difference used when they match. Both arrangements use F = 1 for the ideal two-stream comparison.

Channel geometry and resistance. Gas occupies the first gap. For smooth longitudinal flow, each side has Nchannels × width × gap of open flow area. Dₕ = 2 × width × gap/(width + gap), v = ṁ/(ρA), Re = ρvDₕ/μ and Pr = cₚμ/k. Active area is (Nplates − 2) × length × width. For each separating plate, h = Nu·k/Dₕ and U = 1/(1/hg + Rf,g + thickness/kplate + Rf,a + 1/ha). Sum U × plate area over the separating plates. This distinguishes the one-active-wall end channels from the two-active-wall interior channels in laminar flow.

Laminar flow. Screen at Re < 1,800, 0.5 ≤ Pr ≤ 2, and L/Dₕ ≥ 0.05 Re·max(1, Pr), then interpolate fully developed rectangular-channel isothermal-wall Nu values from Shah and London by gap-to-width ratio α. Inactive walls are adiabatic. Darcy f = 96(1 − 1.3553α + 1.9467α² − 1.7012α³ + 0.9564α⁴ − 0.2537α⁵)/Re. The length test is an entry-length screening criterion.

Turbulent flow. Use Jones’s laminar-equivalent Reynolds number Re* = 64Re/(flaminarRe) in the smooth Darcy factor f = (0.790 ln Re* − 1.64)⁻². For the film estimate, Reis and Altemani use Deq/Dₕ = 2/3 + 11α(2−α)/24 and Fanning f = 0.09290 Reeq⁻⁰·²⁶⁸ in their Gnielinski form. Convert Nu from Deq to Dₕ before computing h. Estimates require 1/39 ≤ α ≤ 1, Re* ≥ 10,000, 10,000 ≤ Reeq ≤ 30,000, Re ≤ 10⁶, 0.5 ≤ Pr ≤ 200 and L/Dₕ ≥ 30. The turbulent film does not distinguish end and interior walls and is ESTIMATE ONLY. Transitional, developing, and out-of-range conditions are NOT RATED.

Pressure drop. Δp = (fL/Dₕ + ΣK)ρv²/2 with Darcy f equal to four times the Fanning factor. A rated core check requires documented core entrance and exit losses referenced to channel velocity, a core-only limit, and an ideal-gas inlet state. The screen uses the predicted channel temperature bounds and pressure loss to check Mach below 0.3 and density within ±5% of the input density. It compares a density-screened loss interval, including a bound on momentum change, against the limit. The starting K values are illustrative. The model uses uniform channel distribution and fixed bulk properties. Verify fouling blockage, gas leakage, condensation, and mechanical limits separately.

Corrugation and measured films. Developed area is projected active area times the measured enlargement factor, or the integrated arc-length ratio for an ideal sinusoidal wave. A geometry-matched data map supplies free area, reference diameter, one- and two-active-wall Nusselt numbers, and Darcy friction. The model interpolates between documented Reynolds points within the supplied temperature and Prandtl envelope, and checks declared viscosity and conductivity limits when supplied. Map predictions are ESTIMATE ONLY. Liquid chevron data and air tests on other corrugations do not qualify a different fired-heater plate.

Pass configurations. Equal-pass serial arrangements use two or three identical modules, each carrying the full gas and air flows. Headers mix the channels between modules. The network checks energy closure and uses documented header and turnaround K for rated connection losses. Explicit serial and parallel paths allow unequal pass counts with prescribed flow splits and common plate dimensions. These results are ESTIMATE ONLY. Passive header balancing, system acceptance, automatic sizing of custom networks, and internally baffled stacks are NOT RATED.

Crossflow. Identical three-plate modules are fed in parallel. Gas and air run at right angles, each with its own flow area and path length. The unmixed model integrates the uniform-UA two-dimensional temperature difference. Smooth both-unmixed flow can qualify within the applicable film envelope. One-mixed and both-mixed arrangements are ESTIMATE ONLY. Both-unmixed corrugated crossflow is also ESTIMATE ONLY and requires separate geometry-matched film maps tested along plate length for gas and plate width for air. Missing or incompatible maps and mixed corrugated crossflow are NOT RATED. Both-mixed target UA uses the first attainable solution before peak effectiveness. The advanced search examines applicable stacks through 64 plates.

System losses. Each side adds irreversible core and documented external losses on a total-pressure basis. Single-path components use Darcy–Weisbach duct losses and component K at the stated reference area. Supported parallel banks share two total-pressure nodes and one station density. Branch paths combine documented fitting losses and developed laminar circular-duct losses. Their common pressure drop is counted once. External components use the APH inlet or core outlet temperature. Static difference equals total loss plus outlet velocity pressure minus inlet velocity pressure. Smooth turbulent rectangular-duct friction, illustrative K, and unqualified pressure inputs are ESTIMATE ONLY where a numerical model is available. Unsupported duct regimes, arbitrary loops, distributed manifolds, fan work, and compressible networks are NOT RATED. Keep core and external loss inventories separate.